Carbon monoxide detector-transmitter

VSKU: VAC-E2608-CO

    This combination does not exist.

    Contact Us

    Calibration: Carbon Monoxide CO
    Sensing method: Long-life electrochemical cell
    Sampling method: Diffusion
    Detection range: 0...1000 ppm CO
    Resolution: 1 ppm CO
    Repeatability: < ± 5%
    Sensor lifetime: > 6 years
    Power supply: 11...30 VDC or 90...265 VAC
    Digital interface: RS485, Modbus RTU protocol
    Analog outputs: 2 × 4-20 mA / 0-10 V, user settable
    Output relays: 2 × SPST relays (closing contact),
    250 VAC / 30 VDC, 5 A max
    Default alarm set-points: 25 ppm / 35 ppm CO
    Enclosure: Light grey ABS plastic, wall mount, IP65
    Dimensions: H85 × W82 × D55 mm
    Operating conditions: -20...+50 °C, 15...90 %RH